Showing posts with label Electrical Q/A. Show all posts
Showing posts with label Electrical Q/A. Show all posts

Why LT motors are delta connected and HT motors are star connected?

Why LT motors are delta connected and HT motors are star connected?
  • There is both reason technical and commercial.
1.     In star, phase current is same as line current. But phase voltage is 1/1.732 times line voltage. So insulation required in case of HT motor is less.

2.     The starting current for motors is 6 to 7 times full load current. So start-up power will be large if HT motors are delta connected. It may cause instability (voltage dip) in case small Power system. In starred HT motor starting current will be less compared to delta connected motor. So starting power is reduced. Starting torque will also be reduced. (It will not be a problem as motors are of high capacity.)

3.    Also as current is less copper (Cu) required for winding will be less.
4.    LT motors are delta connected.
1.    Insulation will not be problem as voltage level is less.
2.    Starting current will not be problem as starting power in all will be less. So no problem of voltage dips.
3.    Starting torque should be large, as motors are of small capacity.

LT motors have winding delta connected.

1. In case it is having star delta starter than they are started as Star connected motor.
2. After it attains 80% of synchronous speed the changeover takes place from star to original configuration    delta.
3. In star the voltages across the winding are lesser that is 1/1.732 times that available in delta so current    is limited.
4. When it goes to delta again voltage is full line voltage so current increase even though it is lesser than     the line current it remains higher than the line current drawn in star connection at reduced voltage. So       cables for motor are sized for this current that is what it draws in delta connection.








Why we can’t store AC in Batteries instead of DC?

Wave form of AC & DC

Why we can’t store AC in Batteries instead of DC.or Can we store AC in batteries instead of DC?

We cannot store AC in batteries because AC changes their polarity up to 50 (When frequency = 50 Hz) or 60 (When frequency = 60 Hz) times in a second. Therefore the battery terminals keep changing Positive (+ve) becomes Negative (-Ve) and vice versa, but the battery cannot change their terminals with the same speed so that’s why we can’t store AC in Batteries.

in addition, when we connect a battery with AC Supply, then It will charge during positive half cycle and discharge during negative half cycle, because the Positive (+ve) half cycle cancel the negative (-Ve) half cycle, so the average voltage or current in a complete cycle is Zero. So there is no chance to store AC in the Batteries.

Good to know:  Average Voltage x Average Current Average Power.

 